MECC PHAYSE Product>>LFPC Series of low-voltage filtering and compensation equipment |
|
LFPC Series of low-voltage filtering and compensation equipment Overview LFPC is suitable for mining companies, mills, shopping malls, hotels, residential communities and other distributed power system to filter harmonics, compensate for reactive power, improve the system Power Factor, save energy, adjust the voltage and reduce line losses. Features Configure intelligent reactive compensation controller, switching mode must be stack switching which means FILO; AC input are equipped with fused knife switches served as input separation and short circuit protection; Input equipped with current transformer and arrester, which can display equipment operating current and absorb over-voltage; Set up 1 to 3 single-tuned filter branches, which use the full partial resonance tuning mode, and use filter-specialized reactor and capacitor. All branches can use our self-developed HPJK-L for three-phase over-current protection, and can adopt Dynamic composite switch or contactor as switching equipment; Can at the same time configure compensating branches; Equipped with SAMWHA Capacitor or other imported brands, or domestic-made high-quality full-film dielectric Self-healing power capacitors, which have advantage such as high reliability, long lifetime, low power loss, low temperature rise. In addition to the stack switching, electrical interlock ensure that when lower order filter branches breakdown, the higher order filter branches are switched out of operation at the same time. Condition of Use installation: Indoor Temperature: -20℃~+45℃ Altitude: Less than 1000m (above1000m should adopt plateau-type components) Humidity : ≤95% (at 25℃) No explosive or flammable medium surrounding; no corrosive gas to damage the insulation and the metal; no conductive dust; No severe vibration and shock at the installation site. Implementation and reference standard IEC 60831-1-am1 ed2.0 GB/T 12747.1-2004 GB/T 12325-2008 GB/T 12326-2008 GB/T 14549-1993 JB/T 7113-1993 Selection Remark For stable loads, the total installed capacity and each branch's capacity can be determined according to the measured harmonic and power factor. We have a professional reactive power testing equipment and we can send our engineer to installation site if possible. For Fluctuating load with huge harmonic current, such as welding, which has frequent starts and stops of nonlinear load, active filter is needed. The equipment can pour in the power grid the opposite phase current with the harmonic source current. In short, we can design a small investment and high efficiency, safe and reliable LFPC according to the customer's site situation, and financial ability. Main technical performance Can operate continuously under 110% of rated voltage, but no bigger. Can operate continuously under 130% of rated current, provided with rated frequency and voltage. Rated current can be computed by the capacitor's rated volume and voltage. Degree of Protection: Indoor (IP2x to IP4x); outdoor (up to IP41) Withstand Voltage: Voltage of 2500V, 50Hz against earth for 1 minute, with no breakdown and no flashover. Insulation: 500V mega-Ohmmeter (100 MΩ range) check the main circuit insulation resistance of the relative should not be less than 1 MΩ, 0.5MΩ if the site is wet. Noise:Less than 45dB. Effects in MaKou steel
The THD falls below 4% in accordance with National standards: THD stayed around 3.5% when equipment was on grid, then jumped to 4.5% after removal.
5th order's current harmonics reduced by 50%, whose effect is obvious: before switched on 5th order's current taked up to 35% of appearant current, then falls to 18% after switched on. Keywords: LFPC Low-Voltage harmonic filter compensating reactive power active harmonic test
|
SHENZHEN MECC PHAYSE ELECTRIC EQUIPMENT CO., LTD |
Copyright 2002-2011 SHENZHEN MECC PHAYSE ELECTRIC EQUIPMENT CO., LTD. All Right Reserved. 粵ICP備11100910號 |